스타벅스 성수점 잔향 측정 보고서 (2026)
멜라민폼 48T 천장 흡음재 시공 전·후 잔향(T20) 실측 보고서. 1 kHz 2.30초 → 0.36초. ISO 3382-2 절차 · DIN 18041 A4 기준. 동성케미컬 × 토넥스.
Licensed by the Ministry of Environment as a measurement agency, we issue official, legally admissible reports. We measure all three tracks—absorption, blocking, masking—with Class 1 instruments and standardized procedures, returning reports usable as-is for occupancy approvals, dispute resolution, and certification submissions.

Five steps from site survey to report issuance. Large spaces: two engineers, one day. Smaller spaces: half a day.
We measure all three tracks with standardized procedures and issue legally admissible reports.
The legally admissible official report and the technical analysis report are delivered separately.
A field reverberation report measured per ISO 3382-2. Download the full report as PDF.
멜라민폼 48T 천장 흡음재 시공 전·후 잔향(T20) 실측 보고서. 1 kHz 2.30초 → 0.36초. ISO 3382-2 절차 · DIN 18041 A4 기준. 동성케미컬 × 토넥스.
Measurement can be requested anytime documentary proof is needed—before or after occupancy, during disputes, or for certification.